Keeping cool under pressure: Improving power quality at a cold storage facility

Customer background

Constellation Cold Logistics operates cold storage warehouse facilities in England. The company had recently installed a solar photovoltaic (PV) system to power and sufficiently cool its warehouse buildings, with the aim of running the cooling systems solely on solar power during the day.

SR Electrical, an electrical wholesaler based in northern England, was involved in addressing the facility’s changing electrical requirements following the addition of solar generation.

Challenges at the customer’s site

There was significant underlying harmonic voltage distortion (THDu) across the site, caused by the accumulation of inverter loads, including Variable Frequency Drives (VFDs), soft starters, office equipment, and battery chargers. While no single transformer generated sufficient harmonic currents to push harmonic voltage distortion beyond acceptable limits, the cumulative effect across the site did exactly that.

During the initial investigation, Merus Power’s local partner, Power Capacitors, attended the site and took electrical readings from distribution board meters and power factor correction (PFC) relays, along with detailed installation notes.

Solar generation had been added to all but one transformer, significantly changing the facility’s power factor correction requirements. As a result, the system needed fast response times, small and accurate compensation steps, and the ability to handle periods of leading power factor and large changes in reactive power demand.

Our Merus® Solution

Power Capacitors proposed replacing the existing traditional power factor correction equipment where required with Merus® A2 Active Harmonic Filters. The filters were configured primarily for dynamic power factor correction, responding to changing reactive power demands caused by the addition of solar generation. At the same time, their harmonic filtering capability reduced harmonic currents at individual transformers, helping lower overall THDu across the site.

Power Capacitors utilized the existing PFC switches to install the Merus® A2 filters. The filters’ suitable IP protection options allowed the team to reuse existing PFC cabinets or mount the filters directly onto walls, depending on the installation environment. This flexibility helped reduce installation costs.

The installation team fitted and commissioned three Merus® A2 units, each with a different installation design. The team completed all three installations on time and within budget.

Two additional filter cubicles were also planned for installation by a third party, pending separate modifications to the new electrical distribution boards.

Quick summary

Segment / Application

Cold storage, refrigerated warehousing

Location

Northern England, United Kingdom

Customer challenge

  • Harmonic voltage distortion
  • Changing power factor requirements
  • Leading power factor conditions
  • Fluctuating reactive power demand

Solution delivered

  • Merus® A2 Active Harmonic Filters
  • Three units installed and commissioned
  • Dynamic power factor correction and harmonic filtering
  • Flexible installation using existing infrastructure

Results at a glance

  • Reduced harmonic voltage distortion
  • Lower mains current requirements
  • Reduced transformer loading
  • More efficient reactive power compensation

Why it matters

  • Higher energy efficiency
  • Reduced electrical equipment stress
  • Longer expected equipment lifespan
  • Lower installation costs

Results after installation

The installation of Merus® A2 Active Harmonic Filters improved the efficiency of locally delivered reactive power compensation, reducing mains current requirements and transformer loading. Furthermore, fast and accurate compensation helped the facility accommodate the changing reactive power requirements of its solar PV system.

In addition to power factor correction, the filters reduced harmonic currents, contributing to lower harmonic voltage distortion across the site. This reduction is expected to increase the lifespan of transformers and other electrical components.

The before-and-after images below demonstrate the reduction in harmonic currents achieved through active harmonic filtering. While the filters were primarily configured for power factor correction, these images illustrate the additional harmonic mitigation benefits of the solution.

Filter 1: Harmonic currents before the installation.
Filter 1: Harmonic currents after the installation.
Filter 2: Harmonic currents before the installation.
Filter 2: Harmonic currents after the installation.
Filter 3: Harmonic currents before the installation.
Filter 3: Harmonic currents after the installation.

Talk to our expert!

Viktoria Mansikkala

Sales Manager, Active Harmonic Filter
Partners, Europe

Find local support!

United Kingdom

Power Capacitors

30 Redfern Road
B11 2BH, Birmingham, UK

www.powercapacitors.co.uk

Contact person

Back to top

Contact us!